Updated June 26, 2025
The Photoionization detector (PID) measures and reports the overall local concentration of volatile organic compounds (VOCs) in the local environment when used with the default configuration within Blackline Live.
This article provides information about configuring the PID sensor in Blackline Live, including specifying a target VOC (single or custom), selecting alarm thresholds, as well as STEL and TWA exposure values.
WARNING: Blackline Safety devices may include default sensor threshold values for convenience; however, these defaults may not align with the regulatory or safety requirements of your jurisdiction. Consult with your Environmental Health and Safety group for your organization’s recommended PID Sensor thresholds and overall sensor configuration.
Blackline Safety recommends always reviewing and updating threshold settings before deploying devices to ensure compliance and to maintain appropriate protection levels for your work environment.
For more information about the PID sensor and Correction Factors (CF), please see the following:
This article contains the following sections:
To display the PID Sensor configuration:
The PID sensor supports just over 1000 predetermined target gases. These gases are listed in alphabetical order by their common name.
To select the gas you want to detect:
If the target gas is a mixture of gases, you can calculate the RF, STEL, and TWA values for the overall mixture. For detailed information on the calculations, please see, VOC Correction Factor Technical Notes.
To configure a custom gas (gas mixture):
To ensure higher accuracy in its response, the PID sensor uses dynamic resolutions—this means that you may need to round the desired thresholds up or down depending on what detection range is required.
For example, a calibration concentration of 75.4 should match the correct resolution range. The 50 to 100 range has a resolution of 0.5, so the correct detection resolution would be 75.5.
The table outlining the ranges and their corresponding resolutions displays in the PID section of the configuration profile.
Enable the continuous zero setting to eliminate the issue of high startup offsets by continuously adjusting the sensor baseline while the device is powered on. By default, the Continuous zero setting is enabled.
Power up the device in a clean environment when this feature is enabled. Blackline recommends that you leave this setting enabled when the alarm thresholds are set over 10 ppm.
The gas alert countdown is an optional feature that creates a time buffer before a high-gas alert is delivered to Blackline Live and monitoring personnel. If you enable the countdown feature, select an option from the available times in the Countdown time listing.
After you make the changes to the PID Sensor configuration, the device receives the configuration update when it is power cycled, either by manually powering the device off then on, or through a standard bump or calibration test.
To confirm the sensor’s settings on the device:
The name and correction factor of the configured target gas displays on the VOC target screen. This same information also displays during the device’s startup sequence.
NOTE: PID readings display in ppm units.
In most places throughout Blackline Live, VOC target gases are represented by the name of the sensor (PID). In areas where the type of target gas may influence monitoring or response protocol, the full name of the target gas is provided. This includes:
If you have any questions or need further assistance, please contact Blackline Technical Support.